MicrogridLoad

The Load used for the Microgrid found in Pogaku et al.[1] and Bidram et al.[2].

Parameters:

  • \(R\) - Resistance

  • \(L\) - Inductance

Variables (External):

  • \(\omega_{ref}\) - Reference Rotor Angle

  • \(v_{D}\) - Incoming Bus Voltage (D)

  • \(v_{Q}\) - Incoming Bus Voltage (Q)

  • \(i_{D}\) - Line Current (D)

  • \(i_{Q}\) - Line Current (Q)

Contributions to external equations:

  • \(0\)    (Reference Rotor Residual)

  • \(-i_{D}\)    (Bus residual term)

  • \(-i_{Q}\)    (Bus residual term)

Internal equations:

  • \(\frac{di_{D}}{dt} = -(\frac{R}{L}) i_{D} + \omega_{ref} i_{Q} + \frac{v_{D1} - v_{D2}}{L}\)

  • \(\frac{di_{Q}}{dt} = -(\frac{R}{L}) i_{Q} + \omega_{ref} i_{D} + \frac{v_{Q1} - v_{Q2}}{L}\)