InverseTimeRelay
An inverse-time overcurrent relay with optional lockout.
Notes
Designed to measure a BranchBreakers terminal current and to drive a BranchBreakers
trip1ortrip2input.Above pickup, the trip rises once \(\int t_\mathrm{op}^{-1}\,dt = 1\), the IEEE C37.112[1] operate criterion.
With lockout, the relay commits to trip once \(x\) passes \(1/2\), so it may measure the current it interrupts.
Model Parameters
Symbol |
Units |
JSON |
Description |
Typical Value |
Note |
|---|---|---|---|---|---|
\(I_\mathrm{pickup}\) |
[p.u.] |
|
Pickup current |
Required |
|
\(D\) |
[-] |
|
Time dial |
Required |
|
\(A\) |
[s] |
|
Curve coefficient |
Required |
|
\(B\) |
[s] |
|
Curve offset |
Required |
|
\(\alpha\) |
[-] |
|
Curve exponent |
Required |
|
\(t_r\) |
[s] |
|
Reset constant |
0.0 |
0 for instantaneous reset |
\(s_\mathrm{lock}\) |
[boolean] |
|
Lockout selector |
|
|
IEEE C37.112 curves:
Curve |
|
|
|
|
|---|---|---|---|---|
Moderately inverse |
0.0515 |
0.1140 |
0.02 |
4.85 |
Very inverse |
19.61 |
0.491 |
2.0 |
21.6 |
Extremely inverse |
28.2 |
0.1217 |
2.0 |
29.1 |
Parameter Validation
All real parameters must be finite.
Model Derived Parameters
Model Ports
Name |
Port |
Init |
Description |
|---|---|---|---|
|
Input |
Known |
Required measured current, real component |
|
Input |
Known |
Required measured current, imaginary component |
|
Output |
Known |
Required trip command |
Model Variables
Internal Variables
Differential
Symbol |
Units |
Description |
Note |
|---|---|---|---|
\(x\) |
[-] |
Relay latch |
Algebraic
Symbol |
Units |
Description |
Note |
|---|---|---|---|
\(s\) |
[-] |
Trip command |
|
External Variables
Differential
None.
Algebraic
Symbol |
Units |
Description |
Note |
|---|---|---|---|
\(I_r\) |
[p.u.] |
Measured current, real component |
|
\(I_i\) |
[p.u.] |
Measured current, imaginary component |
|
Model Equations
Smooth functions: above,
latch,
logistic (\(\sigma\)),
max,
min.
For readability, define:
Internal Equations
Differential
Algebraic
External Equations
None.
Initialization
All internal derivatives initialize to zero.
Monitors
Monitor |
Units |
Description |
Note |
|---|---|---|---|
|
[p.u.] |
Measured current magnitude |
\(\sqrt{I_r^2 + I_i^2}\) |
|
[-] |
Relay latch |
\(x\) |
|
[-] |
Trip command |
\(s\) |